3 function chart – VEGA VEGASWING 51 - contactless electronic switch User Manual
Page 20
Advertising
6
.3 Function chart
The following chart provides an overview of the switching conditions
depending on the adjusted mode and level.
Level
Switching status
Control lamp
Mode max.
Switch closed
Green
Mode max.
Switch open
Red
Mode min.
Switch closed
Green
Mode min.
Switch open
Red
Failure
any
Switch open
flashes red
20
VEGASWING
51 • - contactless electronic switch
6 Set up
30212
-EN