3 function chart – VEGA VEGAVIB 55 - two-wire User Manual
Page 20
6.3 Function chart
VEGAVIB 55 level switch
The following chart provides an overview of the switching
conditions depending on the adjusted mode and level.
Mode on the
sensor
Level
Signal current -
Sensor
Signal lamp -
sensor
max.
Overfill protection
8 mA
Green
max.
Overfill protection
approx. 16 mA
red
min.
Dry run protection
approx. 8 mA
Green
min.
Dry run protection
approx. 16 mA
red
Failure message
(min./max. mode)
any
<2.3 mA
flashes red
VEGAVIB 55 level switch with signal conditioning instru-
ment
1)
The following chart provides an overview of the switching
conditions depending on the adjusted mode of the signal
conditioning instrument and the level.
Note:
Keep in mind that the mode switch of VEGAVIB 55 must be
always set to "max.".
1)
You will find suitable signal conditioning instruments under "Technical data"
20
VEGAVIB 55 - - two-wire
Setup
29304
-EN
-070109