Do not mount the instruments in or above the filling stream. Make sure
that you detect the product surface, not the inflowing product.
Fig. 9: Inflowing liquid
The socket piece should be dimensioned in such a way that the
antenna end protrudes at least 10 mm (0.4 in) out of the socket.
10 mm
>
Fig. 10: Recommended socket mounting
If the reflective properties of the medium are good, you can mount
VEGAPULS
62 on sockets which are higher than the length of the
antenna. You will find recommended values for socket heights in the
following illustration. The socket end should be smooth and burr-free, if
possible also rounded. After installation you must carry out a false
echo storage.
Inflowing medium
Socket
18
VEGAPULS
62 • Foundation Fieldbus