Note:
Measurement in a standpipe is not recommended for very adhesive
products.

Surge or bypass tubes must extend all the way down to the requested
min. level, as measurement is only possible within the tube.

Surge pipe
Make sure you provide the necessary upper vent hole in the surge
pipe. The hole must be aligned so that it and the polarisation marking
on the sensor are in the same plane (see illustration: "Pipe antenna
system in a tank
").

max.

min.

2

1

Fig. 15: Pipe antenna system in a tank. The vent hole in the surge pipe must be
in one plane with the polarisation marking on the sensor.

1

Marking of the polarisation direction

2

Vent holde max. ø 5 mm (0.2 in)

If possible, the antenna diameter of the sensor should correspond to
the inner diameter of the tube. With VEGAPULS 62 this is approx.
40 mm (1.575 in). The sensor can be used with tube diameters
between 40 … 80 mm (1.575 … 3.15 in).

Bypass tube
As an alternative to the surge pipe in the vessel, a tube system outside
of the vessel is possible as a bypass tube. Select during setup the
function "Bypass tube".

Align the sensor in such a way that the polarisation marking on the
process fitting is in the same plane as the tube holes or the tube
connection openings (see illustration: "VEGAPULS in a bypass tube").

VEGAPULS

62 • Foundation Fieldbus

21