VEGA VEGAPULS 62 (≥ 2.0.0 - ≤ 3.8) Foundation Fieldbus User Manual

Page 43

Advertising
background image

The following data are read out or written with this function:

l

Measured value presentation

l

Adjustment

l

Medium

l

Standpipe inner diameter

2)

l

Vessel form

l

Damping

l

Linearisation curve

l

Sensor-TAG

l

Displayed value

l

Unit of measurement

l

Language

The following safety-relevant data are not read out or written:

l

PIN

Copy sensor data

Copy sensor data?

Basic adjustment
If the "Reset" is carried out, the sensor resets the values of the
following menu items to the reset values (see chart):

3)

Function

Reset value

Max. adjustment

0 m(d)

Min. adjustment

30 m(d) (VEGAPULS 61, 63, 65)
35 m(d) (VEGAPULS 62, 66)
70 m(d) (VEGAPULS 68)

Medium

Liquid

Vessel form

not known

Damping

0 s

Linearisation

linear

Sensor-TAG

Sensor

Displayed value

AI-Out

Extended settings

None

Unit of measurement

m(d)

The values of the following menu items are not reset to the reset
values (see chart) with "Reset":

Function

Reset value

Language

no reset

2)

With standpipe versions.

3)

Sensor-specific basic adjustment.

Reset

VEGAPULS

62 • Foundation Fieldbus

43

6 Set up with the indicating and adjustment module PLICSCOM