3

Disconnect the connection cables according to the
operating instructions manual of the respective sensor

4

Loosen the two holding screws with a screwdriver (Torx
size T 10 or slot size 4)

2

1

Fig. 3: Loosen the screws
1

Electronics module

2

Screws (2 pcs.)

5

Pull the previous electronics out by holding the opening
levers.

Note:
Make sure that the housing is not rotated during the electronics
exchange. Otherwise the plug may be in a different position
later.

6

Insert the new oscillator carefully. Make sure that the plug
is in the correct position.

7

Insert the two hold screws and tighten them

8

Connect the connection cables according to the operating
instructions manual of the respective sensor

9

Screw the housing cover back on

The electronics exchange is now finished.

As a rule, the exchange of the electronics must be
documented internally when used in Ex applications.