Load this file with "Save target as" on your PC. Start
PACTware™ and mode in the Service-DTM to the menu item
"E

lectronics exchange". Transfer the XML file into the sensor.

6

.2 Setup procedure, two-wire and four-wire

electronics

As a rule, all settings already carried out on site with the
previous electronics module such as min./max. adjustment,
false echo fade-out etc., must be repeated.

Tip:
For this purpose, use the copy function of the indicating and
adjustment module or the adjustment software PACTware™.

6

.3 Additional setup procedure, four-wire

electronics 4 … 20 mA

With four-wire instruments 4 … 20 mA/HART there is a power
supply electronics in the connection compartment. This
electronics is used for connection to the voltage supply and
delivers the 4 … 20 mA output current. The electronics module
must be adapted to the power supply electronics after an
exchange.

Proceed as follows:

1

Connecting the sensor to voltage supply

2

Connect the PC with PACTware™ via VEGACONNECT 3
to the sensor

3

Connect ammeter with measuring range 20 mA as well as
resolution and accuracy ≤1 µA to the current output

4

Select in the Service-DTM the menu item "Current
calibration
" and start the calibration

Information:
The electronics module starts a calibration procedure and
simulates two current values. These values are influenced by
the power supply electronics and displayed on the ammeter.
Typical values are e.g. 6819 and 18597 µA.

5

Enter the measured current values for the first and second
calibration point into the respective menu items

Adjustment

Current calibration

Electronics module - VEGASON series 60

15

Setup

30206

-

EN