VEGA VEGAPULS 63 (≥ 2.0.0 - ≤ 3.8) Foundation Fieldbus User Manual

Page 34

Advertising
background image

Min. adjustment

0

.00 %

=

5

.000 m(d)

4.000 m(d)

3

Prepare the % value for editing with [OK] and set the cursor to the
requested position with [->]. Set the requested percentage value
with [+] and save with [OK]. The cursor jumps now to the distance
value.

4

Enter the suitable distance value in m for the empty vessel (e.g.
distance from the sensor to the vessel bottom) corresponding to
the percentage value.

5

Save the settings with [OK] and move to "Max. adjustment" with [-
>

]

.

Proceed as follows:

Max. adjustment

100

.00 %

=

1

.000 m(d)

2.000 m(d)

1

Prepare the % value for editing with [OK] and set the cursor to the
requested position with [->]. Set the requested percentage value
with [+] and save with [OK]. The cursor jumps now to the distance
value.

2

Enter the appropriate distance value in m (corresponding to the
percentage value) for the full vessel. Keep in mind that the max.
level must lie below the dead band.

3

Save the settings with [OK] and move to "Medium selection" with
[->]

.

Each product has different reflective properties. In addition, there are
various interfering factors which have to be taken into account:
agitated product surfaces and foam generation (with liquids); dust
generation, material cones and echoes from the vessel wall (with
solids). To adapt the sensor to these different conditions, you should
first select "Liquid" or "Solid".

Medium

Liquid

Information:
With VEGAPULS 63 with electronics version "Increased safety",
"S

olid" is preset as factory setting. However, the instrument should be

used preferably in liquids. In such cases, the medium selection should
be set to "Liquid" during setup.

Carry out max. adjust-
ment

Medium selection

34

VEGAPULS

63 • Foundation Fieldbus

6 Set up with the indicating and adjustment module PLICSCOM

28451

-EN

-120530

Advertising