Error

Cause

Rectification

Instrument does
not appear during
connection setup

Profibus DP cab-
le pole-reversed

Check cable and correct, if necessary

Incorrect termina-
tion

Check termination at the beginning
and end points of the bus and termin-
ate, if necessary, according to the
specification

Instrument not
connected to the
segment

Check and correct, if necessary

In Ex applications, the regulations for the wiring of intrinsically safe
circuits must be observed.

?

E

013

l

no measured value available

à Sensor in boot phase
à Sensor does not find an echo, e.g. due to faulty installation or

wrong parameter adjustment

?

E

017

l

Adjustment span too small

à Carry out a fresh adjustment and increase the distance

between min. and max. adjustment

?

E

036

l

no operable sensor software

à Carry out a software update or send instrument for repair

?

E

041, E042, E043

l

Hardware error, electronics defective

à Exchange the instrument or send it in for repair

?

E

113

l

Communication conflict

à Exchange the instrument or send it in for repair

Depending on the reason for the fault and the measures taken, the
steps described in chapter "Set up" may have to be carried out again.

8

.3 Exchanging the electronics module

If the electronics module is defective, it can be replaced by the user.

Error messages via the
indicating and adjust-
ment module

Reaction after fault rec-
tification

VEGAPULS

63 • Foundation Fieldbus

45

8 Maintenance and fault rectification

28451

-

EN

-120530