VEGA VEGAPULS 63 (≥ 2.0.0 - ≤ 3.8) Foundation Fieldbus User Manual

Page 51

Advertising
background image

-

Average power

< 5 µW

-

Average power with 1 m distance

< 200

nW/cm

2

Max. emitted HF power of the antenna system - Version with increased sensitivity

-

Pulse peak power

< 10

mW

-

Pulse duration

< 2

ns

-

Average power

< 25 µW

-

Average power with 1 m distance

< 1 µW/

cm

2

Measuring accuracy

Resolution, general

max. 1 mm (0.039 in)

Deviation

7)

see diagrams

0,5 m (1.6 ft)

20 m (65.62 ft)

10 mm (0.394 in)

3 mm (0.116 in)

- 3 mm (- 0.116 in)

- 10 mm (- 0.394 in)

0

Fig. 32: Deviation VEGAPULS 63

1,0 m (3.280 ft)

20 m (65.62 ft)

30 mm (1.180 in)

15 mm (0.590 in)

- 15 mm (- 0.590 in)

- 30 mm (- 1.180 in)

0

Fig. 33: Deviation VEGAPULS 63 with increased sensitivity in mm, measuring range in m

Influence of the ambient temperature to the sensor electronics

8

)

7)

Incl. non-linearity, hysteresis and non-repeatability.

8)

Relating to the nominal measuring range, in the temperature range
-40 … +80 °C .

VEGAPULS

63 • Foundation Fieldbus

51

10 Annex

28451

-

EN

-120530