5 Connecting to power supply

5.1 General connection instructions

Always observe the following safety instructions:

l

Connect only in the complete absence of line voltage

l

If overvoltage surges are expected, overvoltage arresters

should be installed

In hazardous areas you should take note of the appropriate

regulations, conformity and type approval certificates of the

sensors and power supply units.

The VEGALOG cards must be powered with extra low voltage

(24 V DC) to keep protection class II. Detailled infromation to

voltage supply is available in the "Technical data" in the

"Supplement". When using a VEGASTAB 593, a reliable

separation from the mains circuits is ensured according to DIN

VDE 0106, part 101.
If voltage supply is not taken over by VEGASTAB, the supply

cable must be looped via the supplied NF filter (type: Schaffner

FN660-10/06). The supply cable after the filter must be wired

with a considerable distance to the signal cables to avoid

couplings.

Note:

Sum the power consumptions of the individual cards and

sensor and select a power supply unit with sufficient power

reserve.

Power supply is connected with standard cable acc. to the

national installation standards.
To connect 4 … 20 mA instruments, standard two-wire cable

without screen can be used. If electromagnetic interference is

expected which is above the test values of EN 61326 for

industrial areas, screened cable should be used.
When connecting Profibus PA sensors, screened cable

according to Profibus specification must be used.
Please make sure that your installation is carried out according

to the Profibus specification. In particular, make sure that the

termination of the bus is done with appropriate terminating

resistors.

Note safety instructions

Take note of safety

instructions for Ex

applications

Select power supply

Selecting the connection ca-

ble