from the instrument catalogue to the project window with a

double click or Drag and Drop. If the project window or the

instrument catalogue are not visible, they can be activated in

the menu bar under " View ".

6.6 Example projects

Project creation VEGALOG and Profibus PA sensor
The following example shows a typical VEGALOG project with

EP card and Profibus sensors. We recommend using the

"VEGA project assistant", this considerably facilitates the

project creation and errors during the address assignment of

the VEGALOG module cards and the sensors are avoided. All

existing cards are found automatically and are added to the

project. Also all connected Profibus sensors are automatically

taken over into the project.
In case the planning is nevertheless carried out manually, e.g.

when creating an offline project, the following DTMs must be

added to the project tree:
1 First of all a driver must be selected by which the

communication via the PC can be carried out. Select the

"VEGA Ethernet" DTM from the instrument catalogue. With

this driver, the connection to VEGACOM 558 in the

VEGALOG 571 processing system is established.
When the "VEGA Ethernet" DTM in the project tree is

selected, you can later adjust the IP address for the

VEGACOM 558 module card in the PACTware™ menu

under "Device data - Add'l functions - Change DTM

addresses". The implementation of this setting is only

possible if a suitable DTM (e.g. VEGACOM 558) has

already been added to the project tree.

2 Finally the DTM "VEGALOG 571" must be added. This

DTM represents the VEGALOG 571 processing system. In

this DTM, measurement loops are created and processed

later on.
When the "VEGALOG 571" DTM in the project tree is

selected, you can later adjust the card addresses for the

VEGALOG module cards in the PACTware™ menu under

"Device data - Add'l functions - Change DTM addresses".

The implementation of this setting is only possible if a

corresponding DTM (e.g. VEGACOM 558) has already

been added to the project tree.

Connection via VE-

GACOM 558/Ethernet

VEGALOG 571 - CPU and carrier

25

Set up

31947

-EN