2 additional instructions for ex applications – VEGA VEGALOG 571 CPU and carrier User Manual

Page 15

Advertising
background image

Connect the cable screen on both ends to ground potential. In

the sensor, the screen must be connected directly to the

internal ground terminal. The ground terminal outside on the

sensor housing must be connected to the potential equal-

isation (low impedance).
If potential equalisation currents are expected, the screen

connection on the side of VEGALOG 571 CPU must be made

via a ceramic capacitor (e.g. 1 nF, 1500 V). The low frequency

potential equalisation currents are thus suppressed, but the

protective effect against high frequency interference signals

remains.
Take note of the corresponding installation regulations for Ex

applications. In particular, make sure that no potential equal-

isation currents flow over the cable screen. In case of

grounding on both sides this can be achieved by the use of a

capacitor or a separate potential equalisation.
The total capacitance of the cable and of all capacitors must

not exceed 10 nF in Ex applications.

5.2 Additional instructions for Ex applications

Applications in the area according to the CENELEC Ex

protective reguations and ElexV (Germany) zone 0 require the

use of approved sensors.
For these applications, not the respective legal documents

(test certificates, test notes and conformity certificates). These

belong to the scope of delivery of the respecitive instrument.
These sensors must only be powered via an intrinsically safe

circuit. With the EA card, the sensors must be connected via a

safety barrier. The EP card is available in Ex version, no

separate separating facility necessary.

Also note the legal documents of these instruments.

To mount, note the following:

l

VEGALOG 571 as well as the used separting facilities

must be only used outside the Ex area.

l

A separating wall must be provided between the con-

nection parts of intrinsically safe and non-intrinsically safe

circuits so that there is a min. distance of 50 mm

l

Only one sensor must be connected to each safety barrier

Cable screening and ground-

ing

Select connection

cable for Ex applica-

tions

Mounting instructions

VEGALOG 571 - CPU and carrier