Linearisation curve

Linear

Enter the requested parameters via the appropriate keys, save your
settings and jump to the next menu item with the [->] key.

In this menu item you can enter an unambiguous designation for the
sensor, e.g. the measurement loop name or the tank or product
designation. In digital systems and in the documentation of larger
plants, a singular designation should be entered for exact identification
of individual measuring points.

Sensor-TAG

Sensor

With this menu item, the Basic adjustment is finished and you can now
jump to the main menu with the [ESC] key.

High sockets or vessel installations, such as e.g. struts or agitators as
well as buildup and weld joints on the vessel walls cause interfering
reflections which can impair the measurement. A false echo storage
detects and marks these false echoes, so that they are no longer taken
into account for the level measurement. A false echo memory should
be created with empty vessel so that all potential interfering reflections
will be detected.

Probes in coax version require no gating out of false echoes since they
are not influenced by false reflections.

False signal suppression

Change now?

Proceed as follows:

1

Move from the measured value display to the main menu by
pushing [OK].

2

Select the menu item "Service" with [->] and confirm with [OK].
Now the menu item "False signal suppression" is displayed.

3

Confirm "False signal suppression - Change now" with [OK] and
select in the below menu "Create new". Enter the actual distance
from the sensor to the product surface. All false signals in this area
are detected by the sensor and saved after confirming with [OK].

Sensor-TAG

False signal suppres-
sion

28

VEGAFLEX

67 • Profibus PA