6 Set up with the display and adjustment module

PLICSRADIO T61 • Wireless emitting unit (single channel)

32865-EN-130322

A instrument address must be assigned to each sensor so that

emitter and receiver can communicate. This address must only be

availabe once per radio channel. Enter an individual address between

1 and 6.
Note:

During operation, the addressing of the individual instruments is no

longer carried out via the device address but via the serial number.

After a change of the device address, the inputs in R61 and C62 must

be reassigned (restart device search).

Enter the values via the appropriate keys and save your settings

with [OK].

To protect the radio connection against unauthorized wiretapping, the

transmission should be protected by a radio PIN. To do that, activate

this function and enter any PIN (0001-9999).

Enter the values via the appropriate keys and save your settings

with [OK].

The displayed value determines which measured value is displayed.

For VEGA sensors "Percent", "lin. percent", "Scaled" and "Sensor

value" are available. The parameterisation of the connected sensor is

based on the settings "Percent", "lin. percent" and "Scaled".
For sensors of other manufacturers, the percentage value is read out

with HART command 2. Only connect instruments supporting this

command correctly.

Enter the values via the appropriate keys and save your settings with

[OK].

When the instrument displays a failure message, further information is

available under the menu item "Diagnosis - Device status".

The service menu contains the following settings:

Configuration of the HART input (active/passive)

Device assignment

Device settings - Address

Device settings - Safe

operating mode

Display - Displayed value

Diagnostics