8 Maintenance and fault rectification

PLICSRADIO T61 • Wireless emitting unit (single channel)

32865-EN-130322

Error code Cause

Rectification

E036

Instrument software

not executable (dur-

ing software update

or after failed update)

– Wait until software update is finished

– Carry out another software update

E042

Hardware error with

selfcheck

– Send instrument for repair

E053

Sensor measuring

range not read cor-

rectly

– Communication error: Check sensor

cable and screening

E086

Error communication

hardware (initiali-

sation of the radio

module failed)

– Initialisation is carried out automati-

cally. If the error exists permanently,

send instrument for repair

Depending on the reason for the fault and the measures taken, the

steps described in chapter "Set up" may have to be carried out again.

8.3 Instrument repair

If a repair is necessary, please proceed as follows:
You can download a return form (23 KB) from our Internet homepage

www.vega.com under: "Downloads - Forms and certificates - Repair

form".
By doing this you help us carry out the repair quickly and without hav-

ing to call back for needed information.

Print and fill out one form per instrument

Clean the instrument and pack it damage-proof

Attach the completed form and, if need be, also a safety data

sheet outside on the packaging

Please ask the agency serving you for the address of your return

shipment. You can find the respective contact data on our website

www.vega.com under: "Company - VEGA worldwide"