VEGA VEGABAR 66 Profibus PA User Manual

Page 53

Advertising
background image

53

10 Supplement

VEGABAR 66 • Profibus PA

36739-EN-130321

Ʋ Ohmic contact

Between ground terminal, process fitting and transmitter

Ʋ Connection cable between IP 68

housing and external electronics

PUR, FEP, PE

Ʋ Type label support with IP 68 version

on cable

PE hard

Weight approx.

Ʋ Basic weight

0.7 kg (1.543 lbs)

Ʋ Suspension cable

0.1 kg/m (0.07 lbs/ft)

Ʋ Connection tube

1.5 kg/m (1 lbs/ft)

Ʋ Straining clamp

0.2 kg (0.441 lbs)

Ʋ Threaded fitting

0.4 kg (0.882 lbs)

Lengths

Ʋ Connection tube

0.25 … 6 m (0.82 … 19.69 ft)

Output variable
Output signal

digital output signal, format according to IEEE-754

Sensor address

126 (default setting)

Current value

10 mA, ±0.5 mA

Dynamic behaviour output
Run-up time approx.

10 s

90 %

100 %

10 %

t

t

T

A

t

t

S

2

1

Fig. 31: Sudden change of the process variable. t

T

: dead time; t

A

: rise time; t

S

: jump response time

1 Process variable

2 Output signal

Dead time

≤ 150 ms

Rise time

≤ 100 ms (10 … 90 %)

Step response time

≤ 250 ms (ti: 0 s, 10 … 90 %)

Damping (63 % of the input variable)

0 … 999 s, adjustable

Additional output parameter - temperature
Processing is made via output signal HART multidrop, Profibus PA and Foundation Fieldbus
Range

-50 … +150 °C (-58 … +302 °F)

Advertising