VEGA VEGABAR 66 Profibus PA User Manual

Page 62

Advertising
background image

62

10 Supplement

VEGABAR 66 • Profibus PA

36739-EN-130321

Tip:

The modules are available in two versions:

Short for Profibus master supporting only one "Identifier Format" byte, e.g. Allen

Bradley

Long for Profibus master only supporting the "Identifier Format" byte, e.g. Siemens

S7-300/400

Examples of telegram configuration

In the following you will see how the modules can be combined and how the appendant data tel-

egram is structured.
Example 1 (standard setting) with pressure value, temperature value and additional cyclical value:

AI (PA-OUT)

Temperature

Additional Cyclic Value

Byte-No.

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

Format

Value

IEEE-754-

Floating point value

PA-OUT

(FB1)

Status

Status

(FB1)

IEEE-754-

Floating point value

Temperature

(FB2)

IEEE-754-

Floating point value

Additional Cyclic

Value

Status

Status

(FB2)

Status

Status

Fig. 35: Telegram configuration example 1

Example 2 with pressure value and temperature value without additional cyclical value:

AI (PA-OUT)

Temperature

Free Place

Byte-No.

1

2

3

4

5

6

7

8

9

10

Format

Value

IEEE-754-

Floating point value

PA-OUT

(FB1)

Status

Status

(FB1)

IEEE-754-

Floating point value

Temperature

(FB2)

Status

Status

(FB2)

Fig. 36: Telegram configuration example 2

Example 3 with pressure value and additional cyclical value without temperature value:

AI (PA-OUT)

Free Place

Additional Cyclic Value

Byte-No.

1

2

3

4

5

6

7

8

9

10

Status

Status

Status

Status

(FB1)

IEEE-754-

Floating point value

PA-OUT

(FB1)

IEEE-754-

Floating point value

Additional Cyclic

Value

Format

Value

Fig. 37: Telegram configuration example 3

Data format of the output signal

Byte4 Byte3 Byte2 Byte1 Byte0

Status

Value (IEEE-754)

Fig. 38: Data format of the output signal

Advertising