When using the profile-specific GSD file, the PA-OUT value as well as the temperature

value are transmitted to the PLC (see block diagram "Cyclical data traffic").

Cyclical data traffic

The master class 1 (e.g. PLC) cyclically reads out measured values from the sensor during opera-

tion. The below block diagram below shows which data can be accessed by the PLC.

bar

%

Lin%

Min-Max

adjustment

Linearization

PROFIBUS PA-output

Primary

Value

Secondary

Value 1

Secondary

Value 2

Target

Mode

Failure

mode

Alarms

Scaling

Source for

scaling

t

i

Damping

Sensor

characteristics

PA-Out

TB

FB

Select additional cyclic

value

Sensor mounting

correction

Fig. 33: VEGABAR 66: Block diagram with AI (PA-OUT) value and Additional Cyclic Value

PROFIBUS PA-output

Target

Mode

Failure

mode

Alarms

Scaling

Source for

scaling

t

i

Damping

Sensor

characteristics

PA-Out

°C

TB

FB 2

Fig. 34: VEGABAR 66: Block diagram with temperature value

Module of the PA sensors

For the cyclic data traffic, VEGABAR 66 provides the following modules:

AI (PA-OUT)

– PA-OUT value of the FB1 after scaling

Temperature

– PA-OUT value of the FB2 after scaling

Additional Cyclic Value

– Additional cyclical value (depending on the source)

Free Place

– This module must be used if a value should not be used in the data telegram of the cyclical

data traffic (e.g. replacement of the temperature and Additional Cyclic Value)

A maximum of three modules can be active. By means of the configuration software of the Profibus

master you can determine the configuration of the cyclical data telegram with these modules. The

procedure depends on the respective configuration software.