VEGA VEGABAR 66 Profibus PA User Manual

Page 55

Advertising
background image

55

10 Supplement

VEGABAR 66 • Profibus PA

36739-EN-130321

The specifications are only an overview and refer to the measuring cell. Limitations due to the ma-

terial and version of the process fitting are possible. The specifications on the nameplate apply.

Nominal range

Overload capacity, max.

pressure

Overload capacity, min. pres-

sure

Gauge pressure
0 … +1.5 psig

+200 psig

-3 psig

0 … +3 psig

+290 psig

-6 psig

0 … +6 psig

+430 psig

-12 psig

0 … +15 psig

+500 psig

-15 psig

0 … +35 psig

+700 psig

-15 psig

0 … +70 psig

+950 psig

-15 psig

0 … +150 psig

+1300 psig

-15 psig

0 … +350 psig

+1900 psig

-15 psig

0 … +900 psig

+2900 psig

-15 psig

Absolute pressure
0 … 15 psi

500 psi

0 psi

0 … 35 psi

700 psi

0 psi

0 … 70 psi

900 psi

0 psi

0 … 150 psi

1300 psi

0 psi

0 … 350 psi

1900 psi

0 psi

Reference conditions and actuating variables (according to DIN EN 60770-1)
Reference conditions according to DIN EN 61298-1

Ʋ Temperature

+15 … +25 °C (+59 … +77 °F)

Ʋ Relative humidity

45 … 75 %

Ʋ Air pressure

860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)

Determination of characteristics

Limit point adjustment according to IEC 61298-2

Characterstic curve

Linear

Reference installation position

upright, diaphragm points downward

Influence of the installation position

< 0.2 mbar/20 Pa (0.003 psig)

Deviation determined according to the limit point method according to IEC 60770

11)

Applies to the digital signal output (HART, Profibus PA, Foundation Fieldbus) as well as to ana-

logue current output 4 … 20 mA and refers to the set span. Turn down (TD) is the ratio nominal

measuring range/set span.
Deviation

Ʋ Turn down 1 : 1 up to 5 : 1

< 0.1 %

Ʋ Turn down > 5 : 1

< 0.02 % x TD

Influence of the product or ambient temperature
Thermal change zero signal and output span

11)

Incl. non-linearity, hysteresis and non-repeatability.