2 information on profibus pa – VEGA VEGABAR 66 Profibus PA User Manual

Page 60

Advertising
background image

60

10 Supplement

VEGABAR 66 • Profibus PA

36739-EN-130321

Ʋ Exd instrument

14 … 32 V DC

Operating voltage with illuminated display and adjustment module

Ʋ Non-Ex instrument

18 … 32 V DC

Ʋ Ex-ia instrument

18 … 24 V DC

Ʋ Exd instrument

18 … 32 V DC

Max. number of sensors on the DP/PA

segment coupler non-Ex/Ex

32/10

Electrical protective measures
Protection rating

Ʋ Transmitter

IP 68 (25 bar)

Ʋ Housing, standard

IP 66/IP 67

20)

Ʋ Aluminium and stainless housing

(optionally available)

IP 68 (1 bar)

21)

Ʋ External housing

IP 65

Overvoltage category

III

Protection class

II

Approvals
Instruments with approvals can have different technical data depending on the version.
For that reason the associated approval documents of these instruments have to be carefully

noted. They are part of the delivery or can be downloaded under www.vega.com via "VEGA Tools"

and "serial number search" as well as via "Downloads" and "Approvals".

10.2 Information on Profibus PA

Instrument master file

The instrument master file (GSD) contains the characteristic data of the Profibus PA instrument.

These data are, e.g. the permissible transmission rates as well as information on diagnostics values

and the format of the measured value outputted by the PA instrument.
A bitmap file is also provided for the Profibus network planning tool. This file is installed automati-

cally when the GSD file is integrated. The bitmap file is used for symbolic indication of the PA instru-

ment in the configuration tool.

Ident number

Each Profibus instrument gets an unambiguous ident number (ID number) from the Profibus user

organisation (PNO). This ID number is also included in the name of the GSD file. For VEGABAR 66

the ID number is 0 x 076F(hex) and the GSD file BR__076F.GSD. As an option to this manufactur-

er-specific GSD file, PNO provides also a general so-called profile-specific GSD file. For VEGABAR

66 you have to use the general GSD file PA139701.GSD. If the general GSD file is used, the sensor

must be set to the profile-specific ident number via the DTM software. By default, the sensor oper-

ates with the manufacturer-specific ID number.

Note:

20)

Instruments with gauge pressure measuring ranges cannot detect the ambient pressure when submerged, e.g.

in water. This can lead to falsification of the measured value.

21)

Only with instruments with absolute pressure ranges.

Advertising