7 Setup with the integrated display and adjustment unit

VEGAMET 391 • With SIL qualification

38704-EN-130228

Note:

Approx. 10 minutes after the last pressing of a key, an automatic reset

to measured value indication is triggered. Any values not confirmed

with [OK] will not be saved.

7.2 Setup steps

Through parameter adjustment, the instrument is adapted to the indi-

vidual application conditions. A measurement loop calibration is the

most important step and should always be carried out. A scaling of

the measured value to the desired physical variable and unit, possibly

including a linearization curve, is often useful. The adaptation of the

relay switching points or the setting of an integration time (damping)

to smooth the measured value are further standard adjustment op-

tions.
A setup assistant is available for easy, convenient setup. It guides the

user through the standard applications and settings step by step.
As a standard feature, the parameterization of the instrument is

locked to protect it against unauthorized operation. The instrument is

unlocked by entering a PIN.
Information:

When using PACTware and the respective DTM, additional settings

can be carried out which are not possible or only partly possible with

the integrated display and adjustment unit. Communication is carried

out via the integrated USB interface. You find further information in

chapter "Set up with PACTware".

After being switched on, VEGAMET 391 mit SIL-Qualifikation first of

all carries out a short self-check. The following steps are carried out:

Internal check of the electronics

indication of the instrument type, firmware version as well as the

instrument TAG (instrument name)

The output signals jump briefly to the set fault value

Then the current measured values will be displayed and outputted.

The measured value indication shows the digital indication value, the

measurement loop name (measurement loop TAG) and the unit. An

analogue bar graph can also be displayed. If flow measurement with

totalizer is activated, an additional indication window with totalizer

becomes available. By pushing the [>] key you can move between the

different indication options.

[OK], you move from the measured value indication into the main

menu. Here, you have the choice between the setup assistant for

the most important settings and the complete classic menu.

At the beginning of every setup or parameter adjustment, you have

the choice of continuing with the setup assistant or the classic menu

Parameter adjustment

Switch-on phase

Measured value indica-

tion

Main menu/Setup assis-

tant/Release operation