27

7 Setup with the integrated display and adjustment unit

VEGAMET 391 • With SIL qualification

38704-EN-130228

The simulation of a measured value is used to check the outputs and

connected components. The simulation can be applied to the percent-

age value, the lin. percentage value and the sensor value.
Note:

Please note that connected system parts (valves, pumps, motors,

control systems) are influenced by the simulation, thus unintentional

plant operating conditions can occur. The simulation is terminated

automatically after approxminately 10 minutes.

Carry out your settings via the appropriate keys and save with

[OK].

There are several reset options available. With a reset to basic setting,

all settings, except the language are reset to default. Other options

are reset of the totalizer as well as switched-on period and relay

malfunction. In addition, a restart of the instrument can be carried out

in this menu.

As a protection against unauthorized changes of the adjusted

parameters, the signal conditioning instrument can be locked via a

PIN. After activation, it is not possible to carry out a parameterization

without entering the previously determined PIN. This locking is valid

for the integrated indicating and adjustment unit and for parameteriza-

tion with PACTware and the respective DTM.

In the menu item "Info" the following information is available:

Sensor type and serial number

Software and hardware version

Calibration date and date of the last change using PC

Features of VEGAMET 391 mit SIL-Qualifikation

Additional adjustment and diagnostics options are available via the

Windows software PACTware and the suitable DTM. Connection is

carried out via the USB interface in the instrument. Further information

Additional adjustments -

Simulation

Additional adjustments

- Reset

Additional settings - PIN

Info

Optional settings