7 Setup with the integrated display and adjustment unit

VEGAMET 391 • With SIL qualification

38704-EN-130228

The relay/current outputs are arranged under "Outputs". The relays

3/4 are integrated in the SIL safety concept, hence only limited adjust-

ment options are available compared to relays 1/2.
First of all select the requested mode ("Overfill protection/Dry run

protection").

Overfill protection: Relay is switched off when the max. level is

exceeded (safe currentless condition), relay is switched on again

when the level falls below the min. level (switch-on point < switch-

off point)

Dry run protection: Relay is switched off when the level falls

below the min. level (safe currentless condition), relay is switched

on again when the max. level is exceeded (switch-on point >

switch-off point)

Due to the SIL rating, the behaviour in case of failure is fix set to "Off".
The following example shows the setting of an overfill protection.

Select the requested mode and save with [OK]. By pushing [->], you

reach the next menu item.

Now enter the switching points for switching the relay on and off.

The current output is used to transfer the measured value to a super-

ordinate system, e.g. a PLC, a process control system or a measured

value indication. This is an active output, i.e. the current is provided

actively. The processing must hence have a passive current input. The

current output must always be connected (see chapter "Connection

steps")
The characteristics of the current output is set to 4 … 20 mA and can-

not be changed due to the SIL rating. The behaviour in case of failure

is permanently set to 0 mA.

In the menu item "Display - Indication value", you can set the re-

quested indication value. The following options are available:

Percent: adjusted measured value without taking a probably

stored linearization into account

Meas. loop - Outputs

- Relay 3/4

Meas. loop - Outputs

- Current output

Display - Displayed value