46

12 Supplement

VEGAMET 391 • With SIL qualification

38704-EN-130228

12 Supplement

12.1 Technical data

General data
Version

Instrument for mounting into front panel, switching cabi-

net or housing

Weight

620 g (1.367 lbs)

Housing materials

Valox 357 XU

Connection terminals

Ʋ Type of terminal

Pluggable spring-loaded terminal with coding

Ʋ Max. wire cross-section

2.5 mm² (AWG 14)

Voltage supply
Operating voltage

20 … 253 V AC, 50/60 Hz, 20 … 253 V DC

Max. power consumption

7 VA; 3 W

Sensor input
Number of sensors

1 x 4 … 20 mA

Input type

Ʋ Active input

Sensor supply through VEGAMET 391 mit SIL-Qualifi-

kation

Measured value transmission

Ʋ 4 … 20 mA

analogue for 4 … 20 mA sensors

Deviation

Ʋ Accuracy

±20 µA (0.1 % of 20 mA)

Terminal voltage

19 … 14.5 V at 4 … 20 mA

Current limitation

approx. 26 mA

Detection line break

≤ 3.6 mA

Detection shortcircuit

≥ 21 mA

Adjustment range 4 … 20 mA sensor

Ʋ Empty adjustment

2.4 … 21.6 mA

Ʋ Full adjustment

2.4 … 21.6 mA

Ʋ min. adjustment delta

16 µA

Connection cable to the sensor

two-wire screened standard cable

Digital input
Quantity

2 x digital input

Input type

Passive

Switching threshold

Ʋ Low

-3 …5 V DC

Ʋ High

11 …30 V DC

Max. input voltage

30 V DC

Max. input current

30 mA