VEGA VEGABAR 52 - climate compensated User Manual
Page 46
Dynamic behaviour output
R
un-up time approx.
10
s
90 %
100 %
10 %
t
t
T
A
t
t
S
2
1
Fig. 18: Sudden change of the process variable, dead time t
T
, rise time t
A
and step response time t
S
1
Process variable
2
Output signal
D
ead time
≤
150
ms
R
ise time
≤
100
ms (10 … 90 %)
S
tep response time
≤
250
ms (ti: 0 s, 10 … 90 %)
D
amping (63 % of the input variable)
0 … 999
s, adjustable
Additional output parameter - temperature
P
rocessing is made via output signal HART multidrop, Profibus PA and Foundation Fieldbus
R
ange
-50 … +150 °C (-58 … +302 °F)
R
esolution
1 °C (1.8 °F)
A
ccuracy
-
in the range of 0 … +100 °C
(+32 … +212 °F)
±
3 K
-
in the range of -50 … 0 °C (-58 … +32 °F)
and +100 … +150 °C (+212 … +302 °F)
typ. ±4 K
Input variable
Adjustment
A
djustment range of the min./max. adjustment relating to the nominal measuring range:
-
percentage value
-10 … 110 %
-
pressure value
-20 … 120 %
46
VEGABAR
52 • 4 … 20
mA/HART - climate compensated
10 S
upplement
35075
-EN
-081209