4 Mounting

VEGAPULS 67 • HART - integrated accumulator

40795-EN-121011

Information:

Keep in mind that for these applications, the sensors are designed

for relatively slow level changes. If the sensor is used on a movable

boom, the max. measuring rate must be observed (see chapter

"Technical data").

Fig. 19: Radar sensors on traverse crane

The mounting location of the radar sensor should be a place where no

other equipment or fixtures cross the path of the microwave signals.
Vessel installations, such as e.g. ladders, limit switches, heating spi-

rals, struts, etc., can cause false echoes and impair the useful echo.

Make sure when planning your measuring site that the radar sensor

has a "clear view" to the measured product.
In case of existing vessel installations, a false echo storage should be

carried out during setup.
If large vessel installations such as struts or supports cause false

echoes, these can be attenuated through supplementary measures.

Small, inclined sheet metal baffles above the installations scatter the

radar signals and prevent direct interfering reflections.

Fig. 20: Cover smooth profiles with deflectors

If there are agitators in the vessel, a false signal suppression should

be carried out with the agitators in motion. This ensures that the

interfering reflections from the agitators are saved with the blades in

different positions.