VEGA VEGAPULS 67 (≥ 2.0.0 - ≥ 4.0.0) HART - integrated accumulator User Manual

Page 59

Advertising
background image

59

11 Supplement

VEGAPULS 67 • HART - integrated accumulator

40795-EN-121011

3

4 2

1

Fig. 47: Data of the input variable
1 Reference plane

2 Measured variable, max. measuring range

3 Antenna length

4 Useful measuring range

Max. measuring range

15 m (49.21 ft)

Recommended measuring range

up to 15 m (49.21 ft)

Accuracy (according to DIN EN 60770-1)
Process reference conditions according to DIN EN 61298-1

Ʋ Temperature

+18 … +30 °C (+64 … +86 °F)

Ʋ Relative humidity

45 … 75 %

Ʋ Air pressure

860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)

Installation reference conditions

Ʋ Min. distance to installations

> 200 mm (7.874 in)

Ʋ Reflector

Plane plate reflector

Ʋ False reflections

Largest false echo 20 dB smaller than the useful echo

Deviation with liquids

See following diagrams