Enter the requested parameters via the appropriate keys, save your
settings and jump to the next menu item with the [ESC] and [->] key.

When a reset is carried out, all settings (with only a few exceptions) are
reset. The exceptions are: PIN, language, lighting, SIL and HART
mode.

The following reset functions are available:

l

Delivery status: Restoring the parameter settings at the time of
shipment from the factory. A created false signal suppression,
user-programmable linearization curve, measured value memory
as well as event memory will be deleted.

l

Basic settings: Resetting of the parameter settings incl. special
and laboratory parameters to the default values of the respective
instrument. Any created false signal suppression, user program-
mable linearization curve, measured value memory as well as
event memory will be deleted.

l

Setup: Resetting of the parameter settings to the default values of
the respective instrument . Order-related settings remain but are
not taken over into the current parameters. User-generated false
signal suppression, user-programmed linearization curve, meas-
ured value memory, echo curve memory as well as event memory
remain untouched. The linearization is set to linear.

l

False signal suppression: Deleting a previously created false
signal suppression. The false signal suppression created in the
factory remains active.

l

Peak values measured value: Resetting of the measured min.
and max. distances to the actual measured value.

Select the requested reset function [->] and confirm with [OK].

The following table shows the default values of VEGAPULS 61:

Additional settings/Re-
set

VEGAPULS

61 • Approval according to LPR radio standard

47