VEGA VEGAPULS 61 (≥ 2.0.0 - ≥ 4.0.0) Foundation Fieldbus Approval according to LPR radio standard User Manual

Page 56

Advertising
background image

Code
Text mes-
sage

Cause

Rectification

PA Dev-
Spec
Diagnosis

F

105

Determine
measured
value

l The instrument is still

in the start phase, the
measured value
could not yet be de-
termined

l Wait for the warm-up

phase

l Duration depending

on the version and
parameter adjust-
ment up to approxi-
mately 3 min.

Bit 6

F

113

Communi-
cation error

l Error in the internal

instrument communi-
cation

l Separate operating

voltage briefly

l Send instrument for

repair

Bit 7

F

125

Unpermis-
sible elect-
ronics tem-
perature

l Temperature of the

electronics in the
non-specified section

l Check ambient tem-

perature

l Isolate electronics
l Use instrument with

higher temperature
range

Bit 8

F

260

Error in the
calibration

l Error in the calibra-

tion carried out in the
factory

l Error in the EEPROM

l Exchange of the

electronics

l Send instrument for

repair

Bit 9

F

261

Error in the
configurati-
on

l Error during setup
l False signal sup-

pression faulty

l Error when carrying

out a reset

l Repeat setup
l Repeat reset

Bit 10

F

264

Installation/
Setup error

l Adjustment not within

the vessel height/
measuring range

l Max. measuring ran-

ge of the instrument
not sufficient

l Check or correct in-

stallation and/or pa-
rameter adjustment

l Use an instrument

with bigger measu-
ring range

Bit 11

F

265

Measure-
ment func-
tion distur-
bed

l Sensor does no lon-

ger carry out a mea-
surement

l Operating voltage too

low

l Check operating vol-

tage

l Carry out a reset
l Separate operating

voltage briefly

Bit 12

The following table shows the error codes and text messages in the
status message "Function check" and provides information on causes
as well as corrective measures.

Function check

56

VEGAPULS

61 • Approval according to LPR radio standard

9 Diagnosis, Asset Management and service

41716

-EN

-120301

Advertising