6 Set up with the display and adjustment module

VEGAFLEX 83 • Modbus and Levelmaster protocol

41838-EN-130314

The instrument carries out an automatic false signal suppression

as soon as the probe is uncovered. The false signal suppression is

always updated.
The menu item "Delete" is used to completely delete an already cre-

ated false signal suppression. This is useful if the saved false signal

suppression no longer matches the metrological conditions in the

vessel.

In the menu item "Lock/unlock adjustment", you can protect the

sensor parameters against unauthorized modification. The PIN is

activated/deactivated permanently.
The following adjustment functions are possible without entering the

PIN:

Select menu items and show data

Read data from the sensor into the display and adjustment mod-

ule.

Caution:

With active PIN, adjustment via PACTware/DTM as well as other

systems is also blocked.
You can change the PIN number under "Additional adjustments -

PIN".

This menu item enables the setting of the requested national lan-

guage.

In the delivery status, the sensor is set to the ordered national lan-

guage.

In this menu item, you define the indication of the measured value

on the display. You can display two different measured values. In this

menu item, you define measured value 1.

The default setting for the displayed value 1 is "Filling height Level".

Lock/unlock setup - Ad-

justment

Display - Menu language

Display - Displayed value

1