VEGA VEGAFLEX 83 Modbus and Levelmaster protocol PFA insulated User Manual

Page 68

Advertising
background image

68

11 Supplement

VEGAFLEX 83 • Modbus and Levelmaster protocol

41838-EN-130314

Accuracy (according to DIN EN 60770-1)
Process reference conditions according to DIN EN 61298-1

Ʋ Temperature

+18 … +30 °C (+64 … +86 °F)

Ʋ Relative humidity

45 … 75 %

Ʋ Air pressure

+860 … +1060 mbar/+86 … +106 kPa

(+12.5 … +15.4 psig)

Installation reference conditions

Ʋ Min. distance to installations

> 500 mm (19.69 in)

Ʋ Vessel

metallic, ø 1 m (3.281 ft), centric installation, process

fitting flush with the vessel ceiling

Ʋ Medium

Water/Oil (dielectric constant ~2.0)

1)

Ʋ Installation

Probe end does not touch the vessel bottom

Sensor parameter adjustment

Gating out of false signals carried out

Typical deviation - Interface measure-

ment

± 5 mm (0.197 in)

Typical deviation - Total level interface

measurement

See following diagrams

Typical deviation - Level measurement

2)3)

See following diagrams

0,2 m

(7.874")

0,1 m

(3.937")

0,04 m

(1.575")

1

L

0

-2 mm

(-0.079")

2 mm

(0.079")

15 mm

(0.591")

-15 mm

(-0.591")

Fig. 35: Deviation VEGAFLEX 83 in rod version (coated) in water
1 Dead band - no measurement possible in this area

L Probe length

Deviation - level measurement from 6 m

probe length

0.5 % of the probe length

1)

with interface measurement = 2.0

2)

Depending on the installation conditions, there can be deviations which can be rectified with an adaptation of

the adjustment or a change of the measured value offset in the DTM service mode

3)

The dead bands can be optimizes by a false signal suppression.