VEGA VEGAFLEX 83 Modbus and Levelmaster protocol PFA insulated User Manual

Page 40

Advertising
background image

40

6 Set up with the display and adjustment module

VEGAFLEX 83 • Modbus and Levelmaster protocol

41838-EN-130314

is displayed as percentage value. The higher the value, the more reli-

able the measurement. Values > 90 % indicate reliable measurement.
If you have selected interface measurement under the menu item

"Setup - Application", then the peak values of the interface meas-

urement are displayed in addition to the peak values of the level

measurement.

In another window you can carry out a reset of the two peak values

separately.

The respective min. and max. measured values are saved in the

sensor. The values are displayed in the menu item "Peak values Ad-

ditional".
This menu item displays the peak values of the electronics tempera-

ture as well as the dielectric constant.

In another window you can carry out a reset of the two peak values

separately.

The menu item "Echo curve" shows the signal strength of the echoes

over the measuring range in V. The signal strength enables an evalua-

tion of the quality of the measurement.

With the following functions you can zoom part sections of the echo

curve.

"X-Zoom": Zoom function for the meas. distance

"Y-Zoom": 1, 2, 5 and 10x signal magnification in "V"

"Unzoom": Reset the presentation to the nominal measuring range

with single magnification

Diagnostics - Peak values

Additional

Diagnostics - Echo curve

Advertising