5 levelmaster commands, Fc43 sub 14, read device identification, Parameters for the bus communication – VEGA VEGAFLEX 83 Modbus and Levelmaster protocol PFA insulated User Manual

Page 80

Advertising
background image

80

11 Supplement

VEGAFLEX 83 • Modbus and Levelmaster protocol

41838-EN-130314

Response:

Parameter

Length

Code/Data

Function Code

1 Byte

0x11

Byte Number

1 Byte

Slave ID

1 Byte

Run Indicator Status

1 Byte

FC43 Sub 14, Read Device Identification

With this function code, the Device Identification can be queried.
Request:

Parameter

Length

Code/Data

Function Code

1 Byte

0x2B

MEI Type

1 Byte

0x0E

Read Device ID Code

1 Byte

0x01 to 0x04

Object ID

1 Byte

0x00 to 0xFF

Response:

Parameter

Length

Code/Data

Function Code

1 Byte

0x2B

MEI Type

1 Byte

0x0E

Read Device ID Code

1 Byte

0x01 to 0x04

Confirmity Level

1 Byte

0x01, 0x02, 0x03, 0x81, 0x82, 0x83

More follows

1 Byte

00/FF

Next Object ID

1 Byte

Object ID number

Number of Objects

1 Byte

List of Object ID

1 Byte

List of Object length

1 Byte

List of Object value

1 Byte

Depending on the Object ID

11.5 Levelmaster commands

The VEGAFLEX 83 is also suitable for connection to the following RTUs with Levelmaster protocol.

The Levelmaster protocol is often called "Siemens" "Tank protocol".

RTU

Protocol

ABB Totalflow

Levelmaster

Kimray DACC 2000/3000

Levelmaster

Thermo Electron Autopilot

Levelmaster

Parameters for the bus communication

The VEGAFLEX 83 is preset with the default values:

Advertising