VEGA VEGAFLEX 86 4 … 20 mA_HART two-wire Rod and cable probe With SIL qualification User Manual

Page 50

Advertising
background image

50

7 Set up with the display and adjustment module

VEGAFLEX 86 • 4 … 20 mA/HART two-wire

44234-EN-130823

In the menu item "Current output mode" you determine the output

characteristics and reaction of the current output in case of failure.

The default setting is output characteristics 4 … 20 mA, failure mode

< 3.6 mA.

In the menu item "Current output Min./Max.", you determine the reac-

tion of the current output during operation.

The default setting is min. current 3.8 mA and max. current 20.5 mA.

If a supplementary electronics with a second current output is im-

plemented in the instrument, then you can adjust the second current

output separately.
In menu item"Current output 2" you specify which measured value

the second current output refers to.

The second current output cannot be used as an output in the sense

of a safety-instrumented application (SIL).
The procedure corresponds to the previous settings of the standard

current output. See "Setup - Current output".

Since the HART variables are very extensive, the indication was

divided into two menu items.

Setup - Current output

mode

Setup - Current output

Min./Max.

Setup - Current output 2

Setup - HART variables

(1)

Advertising