10 Diagnostics and service

VEGAFLEX 86 • 4 … 20 mA/HART two-wire

44234-EN-130823

Information:

Please keep the stated torque so that the max. tensile strength

remains.
6. Enter new probe length and if necessary the new probe type and

then carry out a fresh adjustment (see "Setup procedure, Carry-

ing out min. adjustment - Carrying out max. adjustment").

The rod or cable of the probe can be shortened individually.

1. Mark the requested length with mounted measuring rod.
2. Cable: Loosen the pins on the gravity weight (hexagon 3)
3. Cable: remove the pins
4. Cable: Pull the cable out of the gravity weight
5. Shorten the cable/rod with a cut-off wheel or metal saw at the

marking. Take note of the specifications in the following illustration

when shortening the cable.

6. Cable with gravity weight: Shift the cable according to the drawing

into the gravity weight

7. Cable with gravity weight: Fasten cable with the pins, torque 7 Nm

(5.16 lbf ft)
Cable with centering weight: Fasten cable with the pins, torque

7 Nm (5.16 lbf ft) and fix the clamping part on the centering

weight.

8. Enter new probe length and then carry out a fresh adjustment

(see "Setup procedure, Carrying out min. adjustment - Carrying

out max. adjustment").

4

1

1

2

2

3

A

B

C

45 mm (1.77"

)

100 mm

(3.94"

)

25 mm (0.98"

)

50 mm

(1.97"

)

Fig. 46: Shortening the cable probe
A Gravity weight - cable ø 4 mm

B Gravity weight - cable ø 2 mm

C Centering weight - cable ø 2 mm

1 Pins

2 Thread M8 for eye-bolt

3 Fixing screw - centering weight

Shorten cable/rod