VEGA VEGAFLEX 86 4 … 20 mA_HART two-wire Rod and cable probe With SIL qualification User Manual

Page 51

Advertising
background image

51

7 Set up with the display and adjustment module

VEGAFLEX 86 • 4 … 20 mA/HART two-wire

44234-EN-130823

In the menu "HART variables 1" you can have the first HART value PV

(primary value) and the second HART value SV (secondary value) of

the sensor displayed.
The values cannot be changed in the display and adjustment module.

To change these values, you have to use the adjustment software

PACTware.
HART functions are not relevant for SIL applications.

In the menu "HART variables 2" you can have the third HART value

TV (third value) and the fourth HART value QV (quarter value) of the

sensor displayed.
The values cannot be changed in the display and adjustment module.

To change these values, you have to use the adjustment software

PACTware.
HART functions are not relevant for SIL applications.

The following circumstances cause interfering reflections and can

influence the measurement:

High sockets

Vessel installations such as struts

Note:

A false signal suppression detects, marks and saves these false

signals so that they are no longer taken into account for the level and

interface measurement. We generally recommend carrying out a false

signal suppression to achieve the best possible accuracy. This should

be done with the lowest possible level so that all potential interfering

reflections can be detected.
Proceed as follows:

Enter the actual distance from the sensor to the product surface.

All interfering signals in this section are detected by the sensor and

stored.

Setup - HART variables

(2)

Setup - False signal sup-

pression

Advertising