2 connection – VEGA VEGABAR 81 Modbus and Levelmaster protocol - Operating Instructions User Manual

Page 21

Advertising
background image

21

5 Connecting to power supply and bus system

VEGABAR 81 • Modbus and Levelmaster protocol

46293-EN-131107

5.2 Connection

The voltage supply and signal output are connected via the spring-

loaded terminals in the housing.
The connection to the display and adjustment module or to the inter-

face adapter is carried out via contact pins in the housing.
Information:

The terminal block is pluggable and can be removed from the

electronics. To do this, lift the terminal block with a small screwdriver

and pull it out. When reinserting the terminal block, you should hear it

snap in.

Proceed as follows:
1. Unscrew the housing cover
2. Loosen compression nuts of the cable glands
3. Remove approx. 10 cm (4 in) of the cable mantle (signal output),

strip approx. 1 cm (0.4 in) insulation from the ends of the indi-

vidual wires

4. Insert the cable into the sensor through the cable entry

Fig. 15: Connection steps 5 and 6

5. Insert the wire ends into the terminals according to the wiring plan
Information:

Solid cores as well as flexible cores with wire end sleeves are insert-

ed directly into the terminal openings. In case of flexible cores without

end sleeves, press the terminal from above with a small screwdriver;

the terminal opening is freed. When the screwdriver is released, the

terminal closes again.
6. Check the hold of the wires in the terminals by lightly pulling on

them

Connection technology

Connection procedure

Advertising