10 Supplement

VEGABAR 81 • Modbus and Levelmaster protocol

46293-EN-131107

Accuracy

±1 °C (1.8 °F)

Voltage supply
Operating voltage

8 … 30 V DC

Power consumption

< 500 mW

Interpolation protection

Integrated

Potential connections in the instrument
Electronics

Not non-floating

Ground terminal

Galvanically connected with the process fitting

Electrical protective measures

Housing material

Version

IP-protection class

NEMA protection

Plastic

Single chamber

IP 66/IP 67

NEMA 4X/6P

Double chamber

IP 66/IP 67

NEMA 4X

Aluminium

Single chamber

IP 66/IP 68 (0.2 bar)
IP 68 (1 bar)

NEMA 4X/6P
-

Double chamber

IP 66/IP 67
IP 66/IP 68 (0.2 bar)

NEMA 4X
NEMA 4X

Stainless steel, electro-

polished

Single chamber
Single chamber

IP 69K
IP 66/IP 68 (0.2 bar)

-
NEMA 4X/6P

Stainless steel, investment

casting

Single chamber

IP 66/IP 68 (0.2 bar)
IP 68 (1 bar)

NEMA 4X/6P
NEMA 4X

Double chamber

IP 66/IP 67
IP 66/IP 68 (0.2 bar)

NEMA 4X
NEMA 4X

Stainless steel

Transmitter for external

housing

IP 68 (25 bar)

-

Overvoltage category

III

Protection class

II

Approvals
Instruments with approvals can have different technical data depending on the version.
For that reason the associated approval documents of these instruments must be carefully noted.

They are part of the delivery or can be downloaded under www.vega.com and "VEGA Tools" as

well as under "Downloads" and "Approvals".

10.2 Basics Modbus

Bus description

The Modbus protocol is a communication protocol for the communication between instruments. It is

based on a Master/Slave or Client/Server architecture. By means of Modbus, a Master and several

Slaves can be connected. Each bus participant has an unambiguous address and can send mes-

sages to the bus. This is initiated by the Master, the addessed Slave answers. The versions Ethernet