Bus architecture, Protocol description, Parameters for the bus communication – VEGA VEGABAR 81 Modbus and Levelmaster protocol - Operating Instructions User Manual

Page 64: The vegabar 81 is preset with the default values, 10 supplement

Advertising
background image

64

10 Supplement

VEGABAR 81 • Modbus and Levelmaster protocol

46293-EN-131107

and serial (EIA-232 and EIA-485) as well as the modes ASCII, TCP and RTU are available for the

data transfer. In the RTU and ASCII mode interesting here, data will be transmitted in binary form.

The telegram consists generally of the address, the function, the data as well as the transmission

check.

Bus architecture

In the version Modbus RTU, up to 32 participants can be connected to the bus. The length of the

twisted two-wire cable can be up to 1200 m. The bus must be terminated on both sides at the last

bus participant with a terminating resistor of 120 Ohm. The resistor is already integrated in the

VEGABAR 81 and is activated/deactivated via a slide switch.

4

1

3

3

3

2

+

+

power supply

MODBUS

D0

D1

IS GN

D

USB

+

+

power supply

MODBUS

D0

D1

IS GN

D

USB

+

+

power supply

MODBUS

D0

D1

IS GN

D

USB

1

3 4 5

2

off on

( )

(

)

(-)

(-)

1

3 4 5

2

off on

( )

(

)

(-)

(-)

1

3 4 5

2

off on

( )

(

)

(-)

(-)

Fig. 33: Bus architecture Modbus
1 RTU

2 Connection resistor

3 Bus participant

4 Voltage supply

Protocol description

The VEGABAR 81 is suitable for connection to the following RTUs with Modbus RTU or ASCII

protocol.

RTU

Protocol

ABB Totalflow

Modbus RTU, ASCII

Bristol ControlWaveMicro

Modbus RTU, ASCII

Fisher ROC

Modbus RTU, ASCII

ScadaPack

Modbus RTU, ASCII

Thermo Electron Autopilot

Modbus RTU, ASCII

Parameters for the bus communication

The VEGABAR 81 is preset with the default values:

Parameter

Configurable Values

Default Value

Baud Rate

1200, 2400, 4800, 9600, 19200

9600