VEGA VEGAPULS 63 (≥ 2.0.0 - ≥ 4.0.0) Modbus and Levelmaster protocol User Manual

Page 58

Advertising
background image

58

12 Supplement

VEGAPULS 63 • Modbus and Levelmaster protocol

41364-EN-130228

3

4

2

1

Fig. 45: Data of the input variable
1 Reference plane

2 Measured variable, max. measuring range

3 Length antenna cone

4 Useful measuring range

Standard electronics
Max. measuring range

35 m (114.8 ft)

Recommended measuring range

Ʋ Flange DN 50, 2"

up to 15 m (49.21 ft)

Ʋ Flange DN 80, 3"

up to 35 m (114.8 ft)

Electronics with increased sensitivity
Max. measuring range

75 m (246.1 ft)

Flange DN 50, 2"

up to 15 m (49.21 ft)

Flange DN 80, 3"

up to 35 m (114.8 ft)

Output variable
Output

Ʋ Physical layer

Digital output signal according to standard EIA-485

Ʋ Bus specifications

Modbus Application Protocol V1.1b, Modbus over serial

line V1.02

Ʋ Protocols

Modbus RTU, Modbus ASCII, Levelmaster

Max. transmission rate

9.6 Kbit/s

Accuracy (according to DIN EN 60770-1)
Process reference conditions according to DIN EN 61298-1

Ʋ Temperature

+18 … +30 °C (+64 … +86 °F)

Ʋ Relative humidity

45 … 75 %

Ʋ Air pressure

860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)

Installation reference conditions

Ʋ Min. distance to installations

> 200 mm (7.874 in)