VEGA VEGAPULS 63 (≥ 2.0.0 - ≥ 4.0.0) Modbus and Levelmaster protocol User Manual

Page 59

Advertising
background image

59

12 Supplement

VEGAPULS 63 • Modbus and Levelmaster protocol

41364-EN-130228

Ʋ Reflector

Plane plate reflector

Ʋ False reflections

Biggest false signal, 20 dB smaller than the useful signal

Deviation with liquids

See following diagrams

0,5 m (1.6 ft)

10 mm (0.394 in)

- 10 mm (- 0.394 in)

0

2 mm (0.079 in)

- 2 mm (- 0.079 in)

1 2

3

Fig. 46: Deviation under reference conditions
1 Reference plane

2 Antenna edge

3 Recommended measuring range

Repeatability

≤ ±1 mm

Variables influencing measurement accuracy
Temperature drift - Digital output

±3 mm/10 K relating to the max. measuring range or

max. 10 mm

Additional deviation through electromag-

netic interference acc. to EN 61326

< ±50 mm

Influence of the superimposed gas and pressure to the accuracy
The propagation speed of the radar impulses in gas or vapour above the medium is reduced by

high pressure. This effect depends on the superimposed gas or vapour and is especially large at

low temperatures.
The following table shows the resulting deviation for some typical gases and vapours. The specified

values refer to the distance. Positive values mean that the measured distance is too large, negative

values that the measured distance is too small.

Gas phase

Temperature

Pressure

1 bar

(14.5 psig)

10 bar

(145 psig)

50 bar

(725 psig)

100 bar

(1450 psig)

200 bar

(2900 psig)

Air

20 °C/68 °F

0.00 %

0.22 %

1.2 %

2.4 %

4.9 %

200 °C/392 °F -0.01 %

0.13 %

0.74 %

1.5 %

3.0 %

400 °C/752 °F -0.02 %

0.08 %

0.52 %

1.1 %

2.1 %

Hydrogen

20 °C/68 °F

-0.01 %

0.10 %

0.61 %

1.2 %

2.5 %

200 °C/392 °F -0.02 %

0.05 %

0.37 %

0.76 %

1.6 %

400 °C/752 °F -0.02 %

0.03 %

0.25 %

0.53 %

1.1 %