Abb total flow, Wiring plan, Parameter – VEGA VEGAPULS 63 (≥ 2.0.0 - ≥ 4.0.0) Modbus and Levelmaster protocol User Manual

Page 74: 12 supplement

Advertising
background image

74

12 Supplement

VEGAPULS 63 • Modbus and Levelmaster protocol

41364-EN-130228

ABB Total Flow

Wiring plan

+

+

power supply

MODBUS

D0

D1

IS GND

USB

1

2

13

45

2o

ff

on

( )

()

(-)

(-)

8

1

2

6

7

Bus +

Bus -

GND
VBAT

Fig. 49: Connection of VEGAPULS 63 to RTU ABB Total Flow
1 VEGAPULS 63

2 RTU ABB Total Flow

Parameter

Parameter

Value

Baud Rate

9600

Floating Point Format Code

0

RTU Data Type

16 Bit Modicon

Input Register Base Number

1

The basic number of the input registers is always added to the input register address of VEGAPULS

63.
Address 1303 must hence be entered as register address for 1302 for RTU ABB Total Flow.