VEGA VEGASWING 66 - two-wire With SIL qualification User Manual

Page 19

Advertising
background image

19

5 Connecting to power supply

VEGASWING 66 • - two-wire

44952-EN-130805

9

4

7

1

5

3

2

6

8

on

4

3

2

Test

1

Z

1 2

g / cm3

0,7

0,5

max

min

Fig. 12: Electronics and connection compartment, single chamber housing
1 Control lamp - fault indication (red)

2 Signal lamp - Switching condition (yellow)

3 Signal lamp - Operating condition (green)

4 Mode switch for selecting the switching behaviour (min./max.)

5 DIL switch for sensitivity adjustment

6 Test key

7 Ground terminal

8 Clamp arch

9 Connection terminals

We recommend connecting VEGASWING 66 according to the closed

circuit principle, i.e. the switching circuit is open when there is a level

signal, line break or fault (safe condition).
For connection to a VEGATOR signal conditioning instrument dto.

Ex, WHG. The sensor is powered by the connected VEGATOR signal

conditioning instrument. Further information is available in chapter

"Technical data", "Ex-technical data" are available in the supplied

"Safety information manual".
The wiring example is applicable for all suitable signal conditioning

instruments.
The yellow control lamp on the VEGASWING 66 lights depending on

the adjusted mode.
Take note of the operating instructions manual of the signal condition-

ing instrument. Suitable signal conditioning instruments are listed in

chapter "Technical data".
If VEGASWING 66 is used in Ex areas, take note of the regulations

in the safety instructions and conformity certificates. If the instrument

is to be operated directly on the analogue input of a PLC, a suitable

safety barrier should be connected.

Electronics and connec-

tion compartment

Wiring plan

Advertising