6 Setup

VEGASWING 66 • - two-wire

44952-EN-130805

With the mode adjustment (min./max.) you can determine the output

current.
Note:

When using a VEGATOR signal conditioning instrument, always set

the mode switch (4) to max. mode.
In this case you select the requested mode according to the "Function

chart" (max. - max. detection or overfill protection, min. - min.detection

or dry run detection) on the VEGATOR signal conditioning instrument.
When used on a control system, the following values apply:

Mode min.

– Vibrating element uncovered - 16 mA ±1.5 mA

– Vibrating element covered - 8 mA ±1.5 mA

Mode max.

– Vibrating element uncovered - 8 mA ±1.5 mA

– Vibrating element covered - 16 mA ±1.5 mA

With this DIL switch (5) you can set the switching point to liquids hav-

ing a density between 0.5 and 0.7 g/cm³ (0.018 - 0.025 lbs/in³). With

the basic setting, liquids with a density of ≥ 0.7 g/cm³ (0.025 lbs/in³)

can be detected. In liquids with lower density, you must set the switch

to ≥ 0.5 g/cm³ (0.018 lbs/in³). The specifications for the position of the

switching point relate to water - density value 1 g/cm³ (0.036 lbs/in³).

In products with a different density, the switching point will shift in the

direction of the housing or tuning fork end depending on the density

and type of installation.
Note:

Keep in mind that foams with a density > 0.45 g/cm³ (0.016 lbs/in³)

are detected by the sensor. This can lead to erroneous switchings,

particulary when the sensor is used for dry run protection.
Note:

In case of strong boiling or deployment processes as well as extreme

outgasing, the density of the gas/product mixture on the product

surface can be so low that it can be no longer detected by the sensor.

This can cause faulty switchings.

With key (6) you can activate the test process. You interrupt the volt-

age supply as long as you are pressing the key. The test process will

be carried out after releasing the key.

6.3 Function chart

The following chart provides an overview of the switching conditions

depending on the set mode and the level.
Note:

Keep in mind that the mode switch of VEGASWING 66 must be

always set to "max.".

Mode setting (4)

Sensitivity adjustment (5)

Test key (6)