6 Set up with the display and adjustment module

VEGAFLEX 82 • 4 … 20 mA/HART - four-wire

41830-EN-130314

You can choose between the following medium types:

Dielectric con-

stant

Medium type

Examples

> 3

Cereals, flour

All kind of cereals, wheat flour

1.5 … 3

Granules, cement Lime, gypsum, cement

< 1.5

Dusts, wood chips Wood chips, sawdust

In this menu item, you can enter the max. adjustment for the level.

Adjust the requested percentage value with [+] and save with [OK].

Enter the appropriate distance value in m (corresponding to the

percentage value) for the full vessel. The distance refers to the sensor

reference plane (seal surface of the process fitting). Keep in mind that

the max. level must lie below the dead band.

In this menu item, you can enter the min. adjustment for the level.

Adjust the requested percentage value with [+] and save with [OK].

Enter the suitable distance value in m for the empty vessel (e.g.

distance from the flange to the probe end) corresponding to the per-

centage value. The distance refers tot he sensor reference plane (seal

surface of the process fitting).

Setup - Max. adjustment

Level

Setup - Min. adjustment

Level