7 Setup with PACTware

VEGAFLEX 82 • 4 … 20 mA/HART - four-wire

41830-EN-130314

Information:

In special cases you can change the medium type. This setting can be

changed under "Extended adjustment".
Application

In this field you can select the application you want to use your instru-

ment for. You have the following selection options:

Level in the metallic vessel

Level in the non-metallic vessel

Demonstration mode

Level measurement: If you select "Level", you can select the proper-

ties of the medium in another field.
Demonstration mode: This mode is suitable for test and demonstra-

tion purposes. In this mode, the sensor ignores all logic parameters

and reacts immediately to all measured value changes within the

measuring range.
Application - Level measurement

The level measurement refers to the product surface which is the limit

to the gas phase.

With bulk solids:

– Dusts, wood chips - dielectric constant < 1.5

– Granules, dusts, powders - dielectric constant 1.5 … 3

– Cereals, flour - dielectric constant > 3

Adjustment for the level measurement

If you have selected level measurement in the previous menu, then

you can enter the values for the min. and max. adjustment. The value

to be entered refers to the distance from the sealing surface of the

process fitting (sensor reference plane) to the surface of the product.

A linearization is required if the measured value should be outputted

volume-proportional and not level-proportional. You can find further

linearization types in the extended adjustment.
If you have a non-linear vessel, you can select here the respective

linearization curve.

Linear

Spherical tank

Horizontal cylindrical tank

In addition you have to enter the following vessel dimensions with

non-linear conditions:

Height of the socket h

Vessel height D

In this window you can adjust the output signal. When the function is

inactive, you can change the settings via the "Extended adjustment".

Step 6 of 7

Sensor optimization

Step 3 of 7

Adjustment

Step 4 of 7

Linearization

Step 5 of 7

Setting - Output signal