6 Set up with the display and adjustment module
VEGAFLEX 82 • 4 … 20 mA/HART - four-wire
41830-EN-130314
Since the scaling is very comprehensive, the scaling of the level value
was divided into two menu items.
In menu item "Level 2" you define the scaling format on the display
and the scaling of the level measured value for 0 % and 100 %.
In menu item"Current output, size" you determine which measured
value the current output refers to.
In menu item "Current output, adjustment" you can assign a respec-
tive measured value to the current output.
In the menu item "Current output Min./Max.", you determine the reac-
tion of the current output during operation.
The default setting is min. current 3.8 mA and max. current 20.5 mA.
Setup - Scaling Level 2
Setup - Current output
Size
Setup - Current output,
adjustment
Setup - Current output
Min./Max.