6 exchange or shorten cable/rod – VEGA VEGAFLEX 82 4 … 20 mA_HART four-wire User Manual

Page 60

Advertising
background image

60

9 Diagnostics and service

VEGAFLEX 82 • 4 … 20 mA/HART - four-wire

41830-EN-130314

9.6 Exchange or shorten cable/rod

The cable or rod (meas. part) of the probe can be shortened, if neces-

sary. To loosen the rod or cable you need a fork spanner with spanner

width 13.
1. Loosen the rod or cable by applying a fork spanner to the flat

surfaces (SW 13), provide counterforce with another fork spanner

(SW 13)

2. Unscrew the loosened rod or cable manually.
3. Place the enclosed new double washer onto the thread.
Caution:

Make sure that the two components of the double washer remain

together.
4. Screw the new rod and the new cable manually to the thread on

the process fitting.

5. Exert counterforce with the second fork spanner and tighten the

or or cable on the flat surfaces with a torque of 15 Nm (11 lbf ft).

Fig. 32: Exchange cable or rod

Information:

Please keep the stated torque so that the max. tensile strength

remains.

The rod or cable of the probe can be shortened individually.

1. Mark the requested length with mounted measuring rod.
2. Cable: Loosen the three pins on the gravity weight

Cable ø 4: 6 hexagon 3
Cable ø 6, cable ø 8: hexagon 4

3. Cable: remove the pins
4. Cable: Pull the cable out of the gravity weight
5. Shorten the cable/rod with a cut-off wheel or metal saw at the

marking. Take note of the specifications in the following illustration

when shortening the cable.

Exchanging the cable/rod

Shorten cable/rod

Advertising