background image

16

4 Mounting

VEGAPULS 62 • Modbus and Levelmaster protocol

41362-EN-121011

ficient air flow (the air is led through the holes to the feed system. A

rinsing of the whole parabolic antenna is not intended).

1

2
3

4

Fig. 7: Dismounting, parabolic antenna
1 Connection piece

2 Compression nut

3 Locknut

4 Parabolic antenna

4.4 Instructions for installation

The illustrations with the following mounting instructions show a radar

sensor with horn antenna. The mounting instructions apply analo-

gously also to the version with parabolic antenna.

The emitted radar impulses of the radar sensor are electromagnetic

waves. The polarisation plane is the direction of the electrical wave

component. By turning the instrument in the connection flange or

mounting boss, the polarisation can be used to reduce the effects of

false echoes.
The position of the polarisation plane is marked on the process fitting

of the instrument.

1

2

Fig. 8: Position of the polarisation level
1 Marking with screwed version

2 Marking with flange version

When mounting the sensor, keep a distance of at least 200 mm

(7.874 in) from the vessel wall. If the sensor is installed in the center

of dished or round vessel tops, multiple echoes can arise. However,

these can be suppressed by an appropriate adjustment (see chapter

"Setup").
If you cannot keep this distance you should carry out a false echo

storage before setup. This applies mainly if buildup on the vessel wall

Horn and parabolic

antenna

Polarisation plane

Installation position